130 series products are combined heat meter. The radial impeller flow sensor, which with power supplied by inside lithium battery, is adopted in series products, which not only fit to apply in networking but also fit to apply in independence environment. The distance between the calculator and flow meter should be not more than 10m. The delivery standard length is 1.5m .The wire of temperature sensor is maximum length with 25m and the delivery standard length is 1.5m.The series products with better capability of against magnetism disturbing.
Main parameter and technical data
Basic parameter Environment class CJ128-2000 A ,relative humanity <80%RH Blanket protection grade IP52 Products standard Q/(QY) BCKJ 4-2006 Energy measuring accuracy Class 3 Products structure Combined meter
Display Type and contents display LCD,8 digits Unit kWh - kW - m3/h - m3 -℃ Max-reading 999999.99 Corresponding display content Energy–power– flow– temperature
Temperature input Temp. sensor type PT 1000-two wire Temp. resolution 0.1℃ Temp. measuring range 0℃ ~ 100℃ Measuring range for temp.difference 3K ~ 60K Temp.difference start measuring DN20~DN40 = 1.0K, DN50~DN200 = 0.7K Temp. upper-limit of cooling measuring Delivery default value:15℃ Temp. lower limit of heat measuring Delivery default value:40℃
Flow meter Structure format Radial impeller flow meter Operating pressure ≤1.6MPa Working current ≤100uA Pressure lose ≤10kPa
Network interface Network serial interface M-BUS Communication protocol BASIC enterprise standard or CJ/T188-Network 2004 Communication rate 2400bps
Other interface Chain measuring input Contact without pressure Arrearage cut-off output DC 3V/3mA(should be assorted with BASIC’s MDU-003 to operate)
Power External power supply M-BUS DC 21V~33V, working current<1.5mA Inside lithium battery 1 AA specification 3.6V/2AH Inside lithium battery 2 C specification 3.6V/7.5AH Static working current ≤25uA
Energy measuring Time-segment measuring Yes (delivery setting: no time -segment function) Number of timesegment 4 Quantity recorded for time- segment measuring: 4 independence time-segments energy value Mode for weekend time-segments 1 time-segment, Saturday, Sunday,4 modes to choose Mode for working time time-segments 3 time-segments,Monday ~ Friday ,arbitrary setup to be set within 24 hours everyday
|